Einkaufswagen  |  Kontakt  | 
Internationale Rufnummer++49 (0) 7056-9398-0

Eine gute Adresse für Mess- und Regeltechnik aus einer Hand

Isolated DIN Rail Signal Conditioner


Isolated DIN Rail Signal Conditioner | DRSL-DC2

Isolated DIN Rail Signal Conditioner

160,00 DRSL-DC2

1 year warranty CE RoHS
  • Isolation and Conversion of Process Voltage or Current Signals
  • Power Supply and Signal Isolator for 2-Wire Transmitter
  • Slimline Housing—Only 6 mm (0.24") Wide
  • Multiple Signal Ranges (DIP-Switch Selectable)
  • High Accuracy, <0.05% of Span
  • Fast Response Time <7 ms
Mess- und Prozesstechnik - Verwandte Produkte anzeigen


Click on this link if you need more information about signal conditioning.

The DRSL-DC2 isolated DIN rail signal conditioner provides a competitive choice in terms of both price and technology for galvanic isolation of process voltage or current signals to SCADA systems or PLC equipment. The DRSL-DC2 can be used for signal conversion of standard process voltage or current signals. The unit offers isolation between input, output and supply, provides surge suppression and protects control systems from transients and noise.

The DRSL-DC2 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Factory calibrated measurement ranges are easily configured via DIP switches. When the input is configured for 2-wire transmitter mode, the DRSL-DC2 provides the current loop supply voltage. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).

Current Input
    Measurement Range: 0 to 20.5 mA
    Functional Range: 0 to 23 mA
    Programmable Measurement Ranges: 0 to 20 mA and 4 to 20 mA
    Input Voltage Drop: <1.5V
    2-Wire Transmitter Supply: >17V/20 mA
Voltage Input
    Measurement Range: 0 to 10.25V
    Functional Range: 0 to 11.5V/ 0 to 5.75V
    Programmable Measurement Ranges: 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V
    Input Resistance: ≥500 kΩ

Current Output
    Signal Range: 0 to 20.5 mA (span)
    Programmable Signal Ranges: 0 to 20 mA and 4 to 20 mA
    Load: 23 mA/600 Ω max
    Load Stability: ≤0.01% of span/100 Ω
    Current Limit: ≤28 mA
Voltage Output
    Signal Range: 0 to 10V
    Programmable Signal Ranges: 0 to 10, 2 to 10, 0 to 5 and 1 to 5V
    Load: >10 kΩ min

Supply Voltage (via Power Rail or Connectors): 16.8 to 31.2 Vdc
Power Consumption: 1.2 W max
Internal Consumption: 0.4 W typical/0.65 W max
Isolation: Input/output/supply
Isolation Voltage (Test): 2.5 kVac
Isolation Voltage (Working): 300 Vac
MTBF: >231 years, according to IEC 61709 (SN29500)
Signal/Noise Ratio: >60 dB
Response Time (0 to 90%, 100 to 10%): <7 ms
Span: Corresponds to the presently selected DIP switch output range
Accuracy: <±0.05% of span
Temperature Coefficient: <±0.01% of span/°C
EMC Immunity Influence: <±0.5% of span
Extended EMC Immunity
    NAMUR NE 21, A Criterion, Burst: <±1% of span

Operating Temperature: -25 to 70°C (-13 to 158°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Calibration Temperature: 20 to 28°C (68 to 82°F)
Relative Humidity: 0 to 95% RH non-condensing
Protection Degree: IP20
Installation Area: Pollution degree 2 and measurement/overvoltage category II

Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Weight: 70 g (0.15 lb) approx
DIN Rail Type: DIN EN 60715 - 35 mm
Wire Size: 0.13 x 2.5 mm2/AWG 26 to 12 stranded wire
Screw Terminal Torque: 0.5 Nm
Bestellangaben (Bitte Modellnummer angeben)
Lieferzeit: 1 Woche
RoHS compliant
Isolated DIN rail signal conditioner
Lieferzeit: 1 Woche
RoHS compliant
Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length
Lieferzeit: 4 Wochen
RoHS compliant
Power connector unit, 24 Vdc/2.5 A output to power rail
Lieferzeit: 1 Woche
RoHS compliant
Module stop (screwed onto power rail to support and hold mounted devices)
*Alle Preisangaben in Euro.

Zugehörige Dokumentation:

Download Installation Guide for Signal Conditioners
Download DIN Rail Isolators and Signal Conditioners